Telecom Inverter Main Characteristics
EVS high-frequency power or communication inverters (power UPS) are meticulously designed and optimized with built-in isolation circuitry, including DC-DC and DC-AC isolation, ensuring product stability and meeting power system insulation design requirements. They can meet the high standards of UPS power supplies in power systems, communication systems, and other diverse fields.
Whether in power DC panels, integrated AC/DC power systems, communication power panels, or industrial environments, they provide stable and reliable sinusoidal AC power, ensuring the safe and efficient operation of electrical equipment. Suitable for inverter emergency power supply applications with battery rated voltages of DC24V, DC48V, DC110V, and DC220V.
Telecom Inverter Key Features
| EVSPOWER DC48V Series Specifications | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Rated Power | 1KW | 2KW | 3KW | 4KW | 5KW | 6KW | 8KW | 10KW | 12KW | |
| Rated DC Voltage | DC48V | |||||||||
| Battery Voltage Range (DC40-64V) |
Low voltage warning | 44V | ||||||||
| Low voltage power outage | 42V(40-48V(ADJ) | |||||||||
| Low voltage recovery | 54V | |||||||||
| High voltage power outage | 63V(61-64V ADJ) | |||||||||
| High voltage recovery | 62V | |||||||||
| Low voltage shutdown | 38Vdc | |||||||||
| DC Priority Type | Low voltage switching of battery to mains voltage point | 44V(42-51V) | ||||||||
| Return to the battery supply voltage point after sufficient supply | 52V(48-58V) | |||||||||
| Communication Input & AC Output Characteristics | ||
|---|---|---|
| Communication Input | Rated AC input voltage | AC220V |
| Scope of communication input | 170-280Vac(UPS) / 90-280Vac(APL) | |
| Voltage drop point due to under voltage of the municipal power supply | 170Vac±5V (UPS) / 90Vac±5V (APL) | |
| Under voltage recovery point of municipal power supply | 180Vac±5V (UPS) / 100Vac±5V (APL) | |
| Overvoltage and power failure voltage point of mains power | 280Vac±5V | |
| Overvoltage recovery voltage point of mains power | 270Vac±5V | |
| Communication input frequency | 50HZ/60HZ(ADJ) | |
| Frequency range | 40-65HZ | |
| Single mains power on function | yes | |
| UPS Conversion Time | <5ms(UPS); <13ms(Electrical mode) | |
| AC Output | AC output voltage | 220/230/240Vac±3% ADJ |
| Communication output frequency | 50±1HZ/60±1HZ | |
| Output waveform | Pure sine wave (full voltage range) | |
| Waveform distortion rate | ≤3%(Linear Load) | |
| Inverter peak efficiency | 95% | |
| Dynamic response | (0~100%)≤5% | |
| Power factor | >0.9 | |
| Peak power (surge capability) | Twice the rated power in 3 seconds | |
| Idle power consumption (standby power consumption) | 30W | |
| Power derating | No derating (output power will not decrease with the decrease of battery voltage) | |
| Work Environment | Noise (1 meter) | ≤40dB |
| Environmental temperature for use | -40℃~+50℃ | |
| Storage environment temperature | -40℃~+70℃ | |
| Humidity | 0~90% | |
| Using altitude (m) | ≤ 5000 (If it is higher than 1000, the usage will be reduced by 10% per liter starting from 1000) | |
| Continuous running time | Can run continuously for a long time | |
| Cooling method | Temperature controlled variable speed fan for heat dissipation | |
| Mean time between failures | Not less than 100000 hours | |