1 / 5
Output voltage -48V, Output current 0-30A; Its features include input over/under-voltage protection, output over-current protection, output over-voltage protection.
| Telecom power system technical | ||
| AC Input | Input | Single phase 110/220Vac .50hz |
| Frequency | 50HZ, Range: 45Hz~66Hz | |
| Voltage Range | 80V~300VAC | |
| DC output | Rated current(A) | 30A |
| Max Output Current | 0~30A | |
| Rated power(W) | 1500W | |
| Rated voltage(V) | 110/220V | |
| Equ- charge (V) | 56.4V(42-58Vdc adjustable) | |
| Float voltage(V) | 53.5V(42-58Vdc adjustable) | |
| Output Accuracy(V) | ≤1% | |
| Output ripple voltage | ≤200mV <0-20mHZ> | |
| PF | 0.99@220VAC/30A | |
| Leakage current | ≤1.5mA | |
| Indicator | LCD display | Input/output voltage, Frequency, output current, Environment, Rate |
| Power status | City power, Output, Under voltage, overload voltage | |
| Current Sharing | ±5% from true average current between modules | |
| Load regulation | 2% | |
| Line regulation | 1% | |
| Dimension | 482X270X44mm (D*W*H) | |